Elma 4000/C173 Leak current locator
with Ø 53mm current clamp
In stock Few in stock Not in stock
Elma 4000/D37N is the ideal kit to identify fails to ground in IT and TT nets and leak current in IT, TN and TT nets. The set consist of a 4Hz transmitter and a receiver with a current clamp to pick up the signal and read out the fail to ground or leakage current. Using the transmitter to detect (IT net): The generator is inserted between any phase and ground. The current clamp is connected to the digital receiver and the fault to ground is read out as a percentage (%) of the full generator loop power. The Generator is supplied with 230V and a LED will flash with the signal frequency. Using only the clamp (All nets): The current clamp is connected to the receiver and the leakage current is read directly as mA. The selector is set at 50Hz A/mA and the clamp should enclose all wires including the neutral. Elma 4000/C173 is delivered ready to use in a suitcase with Generator, reciever and current clamp type C173 Ø54mm.
Technical data:
-
Battery:Modtager: 9V batteri (Inkl.)
-
Display:0...1999
-
Display accuracy:+/- 1% + tangens nøjagtighed
-
Supply voltage:Generator: 230V / 45...65Hz / 4VA
-
Impedance:Ca. 32kΩ @ 50Hz
-
Pulse:4Hz signal Kontinuerligt eller puls
-
Voltage on inputs:≤500VAC
-
Output signal:4Hz, ≤30mA, ≤15Vrms
-
Battery:1 pcs, 9V, Inkl.