Elma 4000/D37N is the ideal kit to identify fails to ground in IT and TT nets and leak current in IT, TN and TT nets. The set consist of a 4Hz transmitter and a receiver with a current clamp to pick up the signal and read out the fail to ground or leakage current. Using the transmitter to detect (IT net): The generator is inserted between any phase and ground. The current clamp is connected to the digital receiver and the fault to ground is read out as a percentage (%) of the full generator loop power. The Generator is supplied with 230V and a LED will flash with the signal frequency. Using only the clamp (All nets): The current clamp is connected to the receiver and the leakage current is read directly as mA. The selector is set at 50Hz A/mA and the clamp should enclose all wires including the neutral. Elma 4000/B102 is delivered ready to use in a suitcase with Generator, reciever and current clamp type B102 Ø112mm.

Technical data:

  • 4Hz signal:
    Generator: Kontinuerligt eller puls
  • Battery:
    Modtager: 9V batteri (Inkl.)
  • Display:
    Modtager: 0...1999
  • Display accuracy :
    Modtager: +/- 1% + tangens nøjagtighed
  • Supply voltage:
    Generator: 230V / 45...65Hz / 4VA
  • Impedance:
    Generator: Ca. 32kΩ @ 50Hz
  • Voltage on inputs:
    Generator: ≤500VAC
  • Output signal:
    Generator: 4Hz, ≤30mA, ≤15Vrms
  • Battery:
    1 pcs, 9V, Inkl.