Elma 4000/C173 Leak current locator

with Ø 53mm current clamp

EAN 7090009210183 / EL-NR
Elma 4000/D37N is the ideal kit to identify fails to ground in IT and TT nets and leak current in IT, TN and TT nets. The set consist of a 4Hz transmitter and a receiver with a current clamp to pick up the signal and read out the fail to ground or leakage current. Using the transmitter to detect (IT net): The generator is inserted between any phase and ground. The current clamp is connected to the digital receiver and the fault to ground is read out as a percentage (%) of the full generator loop power. The Generator is supplied with 230V and a LED will flash with the signal frequency. Using only the clamp (All nets): The current clamp is connected to the receiver and the leakage current is read directly as mA. The selector is set at 50Hz A/mA and the clamp should enclose all wires including the neutral. Elma 4000/C173 is delivered ready to use in a suitcase with Generator, reciever and current clamp type C173 Ø54mm.
 
In stock Few in stock Not in stock
1,951.00 EUR
Price incl. VAT 2,438.75 EUR
Add to favorite list
Create new list
Save

Technical data:

Generator:
Supply:
230V / 45...65Hz / 4VA
Output:
4Hz, ≤30mA, ≤15Vrms
Impedance:
32kΩ @ 50Hz
4Hz signal:
Continuous or pulse
Voltage on sockets:
≤500VAC
Reciver:
Supply:
9V battery (incl.)
Display:
0...1999
Accuracy:
+/- 1% + clamp accuracy
Product picture showing
Elma 4000/C173 Leak current locator
  • Product pictures
  • Product pictures

Download

File type EN.pdf
File type NO.pdf
This page uses cookies to calculate traffics and optimize contents